- Description
- Inquiry
Overview
MSC90A DIN Mounted Analog Signal Isolator, Signal Converter Current, voltage input, with input-output-power isolated, transmitting and isolating mA, DC signal to various instruments or DCS, PLC etc control systems.
Feature
- 1 input 1 output, 1 input 2 outputs, 2 inputs 2 outputs
- Transmission accuracy (20°C): (0.2%FS+1) digit
- Temperature shift: 0.0075%FS/°C
- Power-Input-Output isolation: 1.5KVrms, 1min, 50HZ
- Input /Output signal: 4-20ma, 0-20ma, 0-5VDC, 1-5VDC,0-10VDC Relay output; RS485 MODBUS-RTU output
- With LCD indicator or without indicator
- Standard 35mm Rail Installation with pluggable terminals
- Size:109×116.5×18.5mm
- Independent power supply :20-32VDC, AC100-260VAC
Specification
Type | 1 input 1 output, 1 /2input 2 outputs | l Accuracy | +-0.15%FS (20℃) |
Isolated power distributed for transmitter | Temperature shift | 0.0075%/℃ | |
l Input Signal | 4-20mA,0-10ma,0-20mA; | Isolated ability | Input-output-power 1.5KV, 1min, 50Hz |
1-5V,0-5V,0-10VDC; | Insulation resistance | Input-output-power ≥100MΩ/500VDC | |
Input impendence | ≤100Ω when current mA input; | Response time: | 1 output: <0.3S, 2 outputs: <0.5S |
≥250KΩwhen voltage VDC put | l Power supply | AC100-265V(50-60HZ); DC24V(+-10%) | |
Distributed power | 19-25VDC, ≤30mA | Consumption (AC100-265V) | <1.7W/(1 output); <2.2W (2 outputs) |
Max. Input Value | ≤30mA, ≤10.5V | With distributed power | <2.4W(1 output); <3.1W (2 outputs) |
l Output | 4-20mA,0-10mA;0-20mA;1-5V,0-5V,0-10V | Consumption (24VDC) | <2.5W/(1 output); <3W (2 outputs) |
Load resistance | ≤500KΩ when 4-20mA,0-10mA,0-20mA | With distributed power | <3.2W(1 output); <3.9W (2 outputs) |
≥250KΩ when 0-5V,1-5VDC | Case material/Protection | PC/ IP20 | |
≥500KΩ when 0-10VDC | EMC | GB/T18268 (IEC61326-1) | |
Relay Output | 0.6A/125VAC, 2A/30VDC | Size/N.W. | 121.2Xx108x13mm/0.14kg |
.RS485 Output | MODBUS-RTU Protocol | Working T&H | -20 to 60℃/25% to 85%RH |
Rate/Distance | 9.6kps, ≤1Km for RS485 communication | Storage temperature | 40 to 80℃ |
Size (mm)
Order Code
MSC90A: DIN Rail Mount Analog Signal Isolator | |||||||||
Order Code: E.g.: MSC90A-NN11-1N1N-N | Description | ||||||||
MSC90A | -X | X | X | -X | X | X | X | -X | MSC90A: DIN Rail Mount Analog Signal Isolator |
Indicator |
-N | Without indicator | |||||||
-D | With indicator | ||||||||
Type | N | Signal isolator without distrusted power supply for transmitter | |||||||
P | Signal isolator with distributed power supply for transmitter | ||||||||
Input-Output NO. | 11 | 1 Input 1 output | |||||||
12 | 1 input 2 output | ||||||||
22 | 2 Input 2 Output | ||||||||
Input 1 | -1 | 4-20mA(default) | |||||||
-2 | 0-10mA | ||||||||
-3 | 0-20mA | ||||||||
-4 | 0-5VDC | ||||||||
-5 | 1-5VDC | ||||||||
-6 | 0-10VDC | ||||||||
-7 | 4-20mA square root | ||||||||
-8 | 0-10mA square root | ||||||||
-9 | 0-5VDC square root | ||||||||
-0 | 1-5VDC square root | ||||||||
-A | -5 to 5VDC | ||||||||
Input 2 |
N | None | |||||||
… | Please choose correct input type as Input 1’s order code | ||||||||
X | Customized | ||||||||
OUT1 |
1 | 4-20mA (default) | |||||||
2 | 0-10mA | ||||||||
3 | 0-20mA | ||||||||
4 | 0-5VDC | ||||||||
5 | 1-5VDC | ||||||||
6 | 0-10VDC | ||||||||
C | RS485 Output, MODBSU-RTU | ||||||||
X | Customized | ||||||||
OUT 2 |
N | None | |||||||
1 | 4-20ma (default) | ||||||||
2 | 0-10mA | ||||||||
3 | 0-20mA | ||||||||
4 | 0-5VDC | ||||||||
5 | 1-5VDC | ||||||||
6 | 0-10VDC | ||||||||
L | Relay output | ||||||||
X | Customized | ||||||||
Power Supply | -N | 100-260VAC (50-60Hz) | |||||||
-D | 24VDC |