Overview
MSC90T DIN Mounted Temperature Transmitter is DIN mounted with programmable Temperature input, mV, resistor input, with input- output-power isolated, transmitting the signal thermocouple, RTD sensor as analog signal output to various instruments or DCS, PLC etc control systems.
Feature
- 1 input 1 output, 1 input 2 outputs, 2 inputs 2 outputs
- Input: Thermocouple, RTD, Resistor, mV, programmable
- Transmission accuracy (20°C): (0.2%FS+1) digit
- Temperature shift: 0.0075%FS/°C
- Power-Input-Output isolation: 1.5KVrms, 1min, 50HZ
- Input /Output signal: 4-20ma, 0-20ma, 0-5VDC, 1-5VDC,0-10VDC Relay output; RS485 MODBUS-RTU output
- With LCD indicator or without indicator
- Standard 35mm Rail Installation with pluggable terminals
- Size:109×116.5×18.5mm
- Independent power supply :20-32VDC, AC100-260VAC
Specification
| . Input type | Thermocouple, RTD, mV, Resistor | Input Type | Measured Range | |
| . Output Signal | 4-20mA, 0-10mA, 0-20mA; | RTD | Pt100 | -200 to 800℃ |
| 0-5VDC, 1-5VDC, 0-10VDC | CU50 | -50 to150℃ | ||
| Resistor Load (mA output) | RL≤550Ω (4-20, 0-10, 0-20mA) | CU100 | -50 to150℃ | |
| Resistor Load (Vdc output) | RL≥250kΩ (1-5VDC, 0-5VDC) | CU53* | -50 to 150.0℃ | |
| Resistor Load (Vdc output) | RL≥500kΩ (0-10VDC) ,customized | BA1 | -200 to 600.0℃ | |
| Relay Output | 0.6A/125VAC, 2A/30VDC | BA2 | -200 to 600.0℃ | |
| .RS485 Output | MODBUS-RTU Protocol | T.C | K | -200 to 1300℃ |
| Communication rate | 9.6Kbps | T | -200 to 400℃ | |
| Communication distance | max.1km | E | -200 to 1000℃ | |
| . Accuracy | 0.2FS%+1 digit | J | 0 to 1200℃ | |
| Temperature shift | 0.0075%FS/℃ | N | 0 to 1300℃ | |
| Resolution | 0.1℃ | R | 0 to 1600℃ | |
| Response time | 1channel: <0.5, 2 Channels: <1S | S | 0 to 1600℃ | |
| Isolated ability | Input-output-power 1.5KV, 1min, 50Hz | B | 400 to 1800℃ | |
| Insulation resistance | Input-output-power≥100mA at 500VDC | Wre3-25 | 0-2300℃ | |
| Power supply | AC100-265V (50-60HZ); DC24V(+-10%) | Wre5-26 | 0-2300℃ | |
| Power Consumption | ≤3W | F2* | 700-2000℃ | |
| Case material/IP Protection | PC/IP20 |
Resistor |
Linear | 0-400Ω |
| Size | 116.5Xx109x18.5mm | Remote | 30-350Ω | |
| Mounting | DIN35mm | Remote* | 0-350Ω | |
| N.W. | 140g |
mV |
0-20mV | 0-20mV |
| EMC | GB/T18268 industrial application (IEC61326-1) | 0-40mV | 0-40mV | |
| Working temperature | -10 to 50℃; | 0-100mV | 0-100mV | |
| Relative Humidity | 25% to 85%RH | -20 to 20mV* | -20 to 20mV | |
| Storage temperature | -10 to 60℃ (No dew) | -100 to 100mV* | -100-100mV | |
Size (mm)

Order Code
| MSC90T: DIN Rail Mount Universal Temperature Transmitter | ||||||||
| Order Code: E.g.: MSC90T-N11-PN1N-N | Description | |||||||
| MSC90T | -X | -X | -X | X | X | X | MSC90T Universal Temperature Transmitter | |
| Input Type | -N | Without indicator | ||||||
| -D | With indicator | |||||||
| Input-Output NO. | 11 | 1 Input 1 output | ||||||
| 12 | 1 input 2 output | |||||||
| 22 | 2 Input 2 Output | |||||||
| Input 1
|
P | Pt100 (default) | ||||||
| … | Please see below range list for input type order code | |||||||
| -X | Customized | |||||||
|
Input 2 |
N | None | ||||||
| …. | Please see below range list for input type order code | |||||||
| X | Customized | |||||||
|
OUT1
|
1 | 4-20Ma (default) | ||||||
| …. | Please see below list for output order code | |||||||
| C | RS485 Output, Modbus-RTU | |||||||
| X | Customized | |||||||
|
OUT 2 |
N | None | ||||||
| 1 | 4-20ma (default) | |||||||
| ….. | Please see below list for output order code | |||||||
| L | Relay output | |||||||
| X | Customized | |||||||
|
Power Supply |
-N | 100-260VAC (50-60Hz) | ||||||
| -D | 24VDC | |||||||
| Type | Code | Type | Range | Type | Code | Type | Range | |
|
PT100 Input |
P | Pt100 | -200 to 800℃ |
T.C Input |
K | K | -200 to 1300℃ | |
| C | CU50 | -50 to150℃ | T | T | -200 to 400℃ | |||
| C1 | CU100 | -50 to150℃ | E | E | -200 to 1000℃ | |||
| C2* | CU53* | -50 to 150.0℃ | J | J | 0 to 1200℃ | |||
| B1 | BA1 | -200 to 600.0℃ | N | N | 0 to 1300℃ | |||
| B2 | BA2 | -200 to 600.0℃ | R | R | 0 to 1600℃ | |||
|
Resistor Input |
R | Linear | 0-400Ω | S | S | 0 to 1600℃ | ||
| R1 | Remote | 30-350Ω | B | B | 400 to 1800℃ | |||
| R2* | Remote* | 0-350Ω | W3 | Wre3-25 | 0-2300℃ | |||
| R3* | Linear | 0-10kΩ | W5 | Wre5-26 | 0-2300℃ | |||
| mV
Input |
M | 0-20mV | 0-20mV | F2* | F2* | 700-2000℃ | ||
| M1 | 0-40mV | 0-40mV |
Output |
1 | 4-20mA | 4-20mA | ||
| M2 | 0-100mV | 0-100mV | 2 | 0-10mA | 0-10mA | |||
| M3* | -20 to 20mV | -20 to 20mV | 3 | 0-20mA | 0-20mA | |||
| M4* | -100-100mV | -100-100mV | 4 | 0-5VDC | 0-5VDC | |||
| X | Customized | 5 | 1-5VDC | 1-5VDC | ||||
| 6 | 0-10VDC* | 0-10VDC |
F2, CU53, 0-350Ω,0-10KΩ, 0-40mV, -20 t0 20mV, -100 to 100mV input, 0-10VDC output can be not programmed and shifted.





















