MSC80T Intelligent DIN Mount Ioslated Temperature Transmitter

  • Description
  • Inquiry

Overview

MSC80T DIN Mounted Temperature Transmitter is programmable thermocouple, RTD temperature input, with input-output-power isolated, transmitting the signal thermocouple, RTD sensor as analog signal output to various instruments or DCS, PLC etc control systems.

 

Feature

  • 1 input 1 output, 1 input 2 outputs, 2 inputs 2 outputs
  • Programmable thermocouple, RTD input by our programmer
  • Transmission accuracy (20°C): (0.2%FS+1) digit
  • Temperature shift: 0.0075%FS/°C
  • Power-Input-Output isolation: 1.5KVrms, 1min, 50HZ
  • Input /Output signal: 4-20ma, 0-20ma, 0-5VDC, 1-5VDC
  • DIN35mm rail mounting with pluggable terminals
  • Size:12Xx108x13mm
  • Independent power supply :20-32VDC  

 

Specification

. Input type Thermocouple, RTD Input Type Measured Range
. Output Signal 4-20mA, 0-10mA, 0-20mA; 0-5VDC, 1-5VDC RTD Pt100 -200 to 800℃
Resistor Load (mA output) RL≤400Ω (4-20ma, 0-10ma, 0-20ma) CU50 -50 to150℃
Resistor Load (Vdc output) RL≥250kΩ (1-5VDC, 0-5VDC) CU100 -50 to150℃
. Accuracy 0.2FS%+1 digit CU53* -50 to 150.0℃
Temperature shift 0.0075%FS/℃ BA1 -200 to 600.0℃
Min. Resolution 0.1℃ BA2 -200 to 600.0℃
Cold junction -compensation -10 to 50℃ T.C K -200 to 1300℃
Cold junction-comp. accuracy ±1℃ T -200 to 400℃
Response time 50ms up to 90% of final value E -200 to 1000℃
Isolated ability Input-output-power 1.5KV, 1min, 50Hz J 0 to 1200℃
Insulation resistance Input-output-power≥100mΩ at 500VDC N 0 to 1300℃
Power supply DC20-32V R 0 to 1600℃
Power Consumption ≤1W (1 input 1Output); ≤1.4W(1/2Input2Output)  S 0 to 1600℃
Case material/Protection PC/ IP20 B 400 to 1800℃
Size 121.2Xx108x13mm Wre3-25 0-2300℃
Working T&H -10 to 50℃; 25% to 85%RH Wre5-26 0-2300℃
Storage temperature -10 to 60℃ (No dew) F2* 700-2000℃

 

 

Size (mm)

 

Order Code

MSC80T: DIN Rail Mount Universal Temperature Transmitter
Order Code: E.g.: MSC80T-11-PN1N Description
MSC80T -X -X -X X X X MSC80T Universal Temperature Transmitter
Input-Output Number 11 1 Input 1 output
12 1 input 2 output
22 2 Input 2 Output
Input 1

 

P Pt100 (default)
Please see below order code list to choose input type
-X Customized
Input 2 N None
…. Please see below order code list to choose correct code
 

OUT1

1 4-20ma (default)
…. Please see order code list to choose output type
 

 

OUT 2

N None
1 4-20ma (default)
….. Please see below order code list to choose output type
X Customized
Input Order Code List
Input

Code

Type

(RTD)

Measured Range Range Accuracy Input

Code

Type

(T.C.)

Measured Range Range Accuracy
P Pt100 – 200 to 650℃ ≤100℃ 0.2% K K -200-1300℃ ≤300℃ 0.2%
100≥℃ 0.1% 300≥℃ 0.1%
C CU50 -50 to150℃ ≤100℃ 0.2% T T -200-400℃ ≤300℃ 0.2%
100≥℃ 0.1% 300≥℃ 0.1%
C1 CU100 -50 to150℃ ≤100℃ 0.2% E E -200-1000℃ ≤300℃ 0.2%
100≥℃ 0.1% 300≥℃ 0.1%
C2* CU53* -50 to 150.0℃ ≤100℃ 0.2% J J 0-1200℃ ≤300℃ 0.2%
100≥℃ 0.1% 300≥℃ 0.1%
B1 BA1 -200 to 600.0℃ ≤100℃ 0.2% N N 0- 1300℃ ≤500℃ 0.2%
100≥℃ 0.1% 500≥℃ 0.1%
B2 BA2 -200 to 600.0℃ ≤100℃ 0.2% R R 0-1600℃ ≤500℃ 0.2%
100≥℃ 0.1% 500≥℃ 0.1%
Output Order Code list  S  S 0-1600℃ ≤500℃ 0.2%
Order Code Output Type 500≥℃ 0.1%
1 4-20mA B B 400-1800℃ ≤500℃ 0.2%
2 0-10mA 500≥℃ 0.1%
3 0-20mA W3 Wre3-25 0-2300℃ ≤500℃ 0.2%
4 0-5VDC 500≥℃ 0.1%
5 1-5VDC W5 Wre5-26 0-2300℃ ≤500℃ 0.2%
X Customized 500≥℃ 0.1%
Note: above accuracy is based 20±2℃, thermocouple cold junction compensation’ accuracy should be considered ≤1℃ F2* F2* 700-2000℃ ≤1000℃ 0.2%
1000≥℃ 0.1%

 

Contact Us