- Description
- Inquiry
Overview
MSC80T DIN Mounted Temperature Transmitter is programmable thermocouple, RTD temperature input, with input-output-power isolated, transmitting the signal thermocouple, RTD sensor as analog signal output to various instruments or DCS, PLC etc control systems.
Feature
- 1 input 1 output, 1 input 2 outputs, 2 inputs 2 outputs
- Programmable thermocouple, RTD input by our programmer
- Transmission accuracy (20°C): (0.2%FS+1) digit
- Temperature shift: 0.0075%FS/°C
- Power-Input-Output isolation: 1.5KVrms, 1min, 50HZ
- Input /Output signal: 4-20ma, 0-20ma, 0-5VDC, 1-5VDC
- DIN35mm rail mounting with pluggable terminals
- Size:12Xx108x13mm
- Independent power supply :20-32VDC
Specification
. Input type | Thermocouple, RTD | Input Type | Measured Range | |
. Output Signal | 4-20mA, 0-10mA, 0-20mA; 0-5VDC, 1-5VDC | RTD | Pt100 | -200 to 800℃ |
Resistor Load (mA output) | RL≤400Ω (4-20ma, 0-10ma, 0-20ma) | CU50 | -50 to150℃ | |
Resistor Load (Vdc output) | RL≥250kΩ (1-5VDC, 0-5VDC) | CU100 | -50 to150℃ | |
. Accuracy | 0.2FS%+1 digit | CU53* | -50 to 150.0℃ | |
Temperature shift | 0.0075%FS/℃ | BA1 | -200 to 600.0℃ | |
Min. Resolution | 0.1℃ | BA2 | -200 to 600.0℃ | |
Cold junction -compensation | -10 to 50℃ | T.C | K | -200 to 1300℃ |
Cold junction-comp. accuracy | ±1℃ | T | -200 to 400℃ | |
Response time | 50ms up to 90% of final value | E | -200 to 1000℃ | |
Isolated ability | Input-output-power 1.5KV, 1min, 50Hz | J | 0 to 1200℃ | |
Insulation resistance | Input-output-power≥100mΩ at 500VDC | N | 0 to 1300℃ | |
Power supply | DC20-32V | R | 0 to 1600℃ | |
Power Consumption | ≤1W (1 input 1Output); ≤1.4W(1/2Input2Output) | S | 0 to 1600℃ | |
Case material/Protection | PC/ IP20 | B | 400 to 1800℃ | |
Size | 121.2Xx108x13mm | Wre3-25 | 0-2300℃ | |
Working T&H | -10 to 50℃; 25% to 85%RH | Wre5-26 | 0-2300℃ | |
Storage temperature | -10 to 60℃ (No dew) | F2* | 700-2000℃ |
Size (mm)
Order Code
MSC80T: DIN Rail Mount Universal Temperature Transmitter | |||||||||||||||||
Order Code: E.g.: MSC80T-11-PN1N | Description | ||||||||||||||||
MSC80T | -X | -X | -X | X | X | X | MSC80T Universal Temperature Transmitter | ||||||||||
Input-Output Number | 11 | 1 Input 1 output | |||||||||||||||
12 | 1 input 2 output | ||||||||||||||||
22 | 2 Input 2 Output | ||||||||||||||||
Input 1
|
P | Pt100 (default) | |||||||||||||||
… | Please see below order code list to choose input type | ||||||||||||||||
-X | Customized | ||||||||||||||||
Input 2 | N | None | |||||||||||||||
…. | Please see below order code list to choose correct code | ||||||||||||||||
OUT1 |
1 | 4-20ma (default) | |||||||||||||||
…. | Please see order code list to choose output type | ||||||||||||||||
OUT 2 |
N | None | |||||||||||||||
1 | 4-20ma (default) | ||||||||||||||||
….. | Please see below order code list to choose output type | ||||||||||||||||
X | Customized | ||||||||||||||||
Input Order Code List | |||||||||||||||||
Input
Code |
Type
(RTD) |
Measured Range | Range | Accuracy | Input
Code |
Type
(T.C.) |
Measured Range | Range | Accuracy | ||||||||
P | Pt100 | – 200 to 650℃ | ≤100℃ | 0.2% | K | K | -200-1300℃ | ≤300℃ | 0.2% | ||||||||
100≥℃ | 0.1% | 300≥℃ | 0.1% | ||||||||||||||
C | CU50 | -50 to150℃ | ≤100℃ | 0.2% | T | T | -200-400℃ | ≤300℃ | 0.2% | ||||||||
100≥℃ | 0.1% | 300≥℃ | 0.1% | ||||||||||||||
C1 | CU100 | -50 to150℃ | ≤100℃ | 0.2% | E | E | -200-1000℃ | ≤300℃ | 0.2% | ||||||||
100≥℃ | 0.1% | 300≥℃ | 0.1% | ||||||||||||||
C2* | CU53* | -50 to 150.0℃ | ≤100℃ | 0.2% | J | J | 0-1200℃ | ≤300℃ | 0.2% | ||||||||
100≥℃ | 0.1% | 300≥℃ | 0.1% | ||||||||||||||
B1 | BA1 | -200 to 600.0℃ | ≤100℃ | 0.2% | N | N | 0- 1300℃ | ≤500℃ | 0.2% | ||||||||
100≥℃ | 0.1% | 500≥℃ | 0.1% | ||||||||||||||
B2 | BA2 | -200 to 600.0℃ | ≤100℃ | 0.2% | R | R | 0-1600℃ | ≤500℃ | 0.2% | ||||||||
100≥℃ | 0.1% | 500≥℃ | 0.1% | ||||||||||||||
Output Order Code list | S | S | 0-1600℃ | ≤500℃ | 0.2% | ||||||||||||
Order Code | Output Type | 500≥℃ | 0.1% | ||||||||||||||
1 | 4-20mA | B | B | 400-1800℃ | ≤500℃ | 0.2% | |||||||||||
2 | 0-10mA | 500≥℃ | 0.1% | ||||||||||||||
3 | 0-20mA | W3 | Wre3-25 | 0-2300℃ | ≤500℃ | 0.2% | |||||||||||
4 | 0-5VDC | 500≥℃ | 0.1% | ||||||||||||||
5 | 1-5VDC | W5 | Wre5-26 | 0-2300℃ | ≤500℃ | 0.2% | |||||||||||
X | Customized | 500≥℃ | 0.1% | ||||||||||||||
Note: above accuracy is based 20±2℃, thermocouple cold junction compensation’ accuracy should be considered ≤1℃ | F2* | F2* | 700-2000℃ | ≤1000℃ | 0.2% | ||||||||||||
1000≥℃ | 0.1% |